| Plan Review Notes For Permit 04041627 |
| Permit Number |
04041627 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-08-12 00:00:00 | DENIED | | | | | | 1) ON SHEET A-9 LOWER ROOF PLAN, TRUSS | | | AT4 ON THE LEFT SIDE OF THE PLAN HAS ITS | | | UPLIFT AND CONNECTOR SPECIFIED AT THE | | | ADJACENT TRUSS, WHICH HAS A MUCH LOWER | | | UPLIFT. | | | | | | 2) THE UPLIFT FOR ONE END OF TRUSS AT16 | | | IN THE TRUSS DRAWINGS EXCEEDS THE | | | CAPACITY OF THE ANCHOR SPECIFIED ON | | | SHEET 9 OF THE PLANS. | | | | | | 3) TRUSSES AT19 AND AT20 ON A-9 EXCEED | | | THE CONNECTOR CAPACITY. | | | | | | 4) ON SHEET A-10 TRUSS BT48 EXCEEDS THE | | | UPLIFT CAPACITY OF THE SPECIFIED | | | CONNECTOR. | | | | | | 5) ON SHEET A-10 TRUSS BT42 HAS AN | | | UPLIFT ON TRUSS DRAWINGS THAT EXCEEDS | | | THE ONE GIVEN ON THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|