Plan Review Notes
Plan Review Notes For Permit 04041627
Permit Number 04041627
Review Stop B
Sequence Number 4
Notes
Date Text
2004-08-12 00:00:00DENIED
  
 1) ON SHEET A-9 LOWER ROOF PLAN, TRUSS
 AT4 ON THE LEFT SIDE OF THE PLAN HAS ITS
 UPLIFT AND CONNECTOR SPECIFIED AT THE
 ADJACENT TRUSS, WHICH HAS A MUCH LOWER
 UPLIFT.
  
 2) THE UPLIFT FOR ONE END OF TRUSS AT16
 IN THE TRUSS DRAWINGS EXCEEDS THE
 CAPACITY OF THE ANCHOR SPECIFIED ON
 SHEET 9 OF THE PLANS.
  
 3) TRUSSES AT19 AND AT20 ON A-9 EXCEED
 THE CONNECTOR CAPACITY.
  
 4) ON SHEET A-10 TRUSS BT48 EXCEEDS THE
 UPLIFT CAPACITY OF THE SPECIFIED
 CONNECTOR.
  
 5) ON SHEET A-10 TRUSS BT42 HAS AN
 UPLIFT ON TRUSS DRAWINGS THAT EXCEEDS
 THE ONE GIVEN ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW