Plan Review Notes
Plan Review Notes For Permit 04041627
Permit Number 04041627
Review Stop P
Sequence Number 2
Notes
Date Text
2004-07-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA-98 DESIGN MANUAL
  
 A) COMMENTS FROM THE PREVIOUS REVIEW
 WERE NOT ADDRESSED, OR NOT ADDRESSED
 PROPERLY.
 1) SHT A-8 SHOW BACKING FOR GRAB BARS AT
 WATER CLOSETS. SEE PAGES 6.4 & 6.5 OF
 THE DESIGN MANUAL. COMMENT RESPONSE
 NOTED, BUT WAS NOT SUFFICIENT.
 2) SHT A-12 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 D) MAXIMUM DFU ON 2" WET VENT IS 4 PER
 TABLE 909.3. MASTER BATH SHOWS 6 DFU'S
 ON 2" PIPE. NO RESPONSE NOTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]