| Plan Review Notes For Permit 04041627 |
| Permit Number |
04041627 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FHA-98 DESIGN MANUAL | | | | | | A) COMMENTS FROM THE PREVIOUS REVIEW | | | WERE NOT ADDRESSED, OR NOT ADDRESSED | | | PROPERLY. | | | 1) SHT A-8 SHOW BACKING FOR GRAB BARS AT | | | WATER CLOSETS. SEE PAGES 6.4 & 6.5 OF | | | THE DESIGN MANUAL. COMMENT RESPONSE | | | NOTED, BUT WAS NOT SUFFICIENT. | | | 2) SHT A-12 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. | | | D) MAXIMUM DFU ON 2" WET VENT IS 4 PER | | | TABLE 909.3. MASTER BATH SHOWS 6 DFU'S | | | ON 2" PIPE. NO RESPONSE NOTED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|