Plan Review Notes
Plan Review Notes For Permit 04041627
Permit Number 04041627
Review Stop P
Sequence Number 1
Notes
Date Text
2004-05-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 AMEND. DESIGN MANUAL
  
 1) SHT A-8 SHOW BACKING FOR GRAB BARS AT
 WATER CLOSETS. SEE PAGES 6.4 & 6.5 OF
 THE DESIGN MANUAL.
 2) SHT A-12 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS:
 A) BOTH BATH #2 SHOWER IS SHOWN TO THE
 RIGHT OF THE WATER CLOSET AND LAV TO THE
 LEFT ON THE FLOOR PLAN. SECTION 104.2.1
 B) LAUNDRY TRAY AND WASH MACHINE SHALL
 DISCHARGE DOWNSTREAM OF THE WET VEN FOR
 THE POWDER ROOM PER SECTION 909.1
 C) PER TABLE 906.1 THE MAXIMUM DISTANCE
 FROM THE TRAP TO THE VENT IS 6'. THE
 WASH MACHINE APPEARS TO BE LONGER. THE
 FLOOR LAYOUT INDICATES THAT SEPARATE
 STACKS SHOULD WORK.
 D) MAXIMUM DFU ON 2" WET VENT IS 4 PER
 TABLE 909.3. MASTER BATH SHOWS 6 DFU'S
 ON 2" IN BOTH MASTER BATHS.
 E) LAVS ARE ON SEPARATE WALLS IN MASTER
 BATHS AND REQUIRE SEPARATE STACKS FOR
 EACH. MAXIMUM 5' FROM TRAP TO VENT PER
 TABLE 906.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]