| Plan Review Notes For Permit 04041627 |
| Permit Number |
04041627 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FHA-98 AMEND. DESIGN MANUAL | | | | | | 1) SHT A-8 SHOW BACKING FOR GRAB BARS AT | | | WATER CLOSETS. SEE PAGES 6.4 & 6.5 OF | | | THE DESIGN MANUAL. | | | 2) SHT A-12 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | | MEET CODE REQUIREMENTS: | | | A) BOTH BATH #2 SHOWER IS SHOWN TO THE | | | RIGHT OF THE WATER CLOSET AND LAV TO THE | | | LEFT ON THE FLOOR PLAN. SECTION 104.2.1 | | | B) LAUNDRY TRAY AND WASH MACHINE SHALL | | | DISCHARGE DOWNSTREAM OF THE WET VEN FOR | | | THE POWDER ROOM PER SECTION 909.1 | | | C) PER TABLE 906.1 THE MAXIMUM DISTANCE | | | FROM THE TRAP TO THE VENT IS 6'. THE | | | WASH MACHINE APPEARS TO BE LONGER. THE | | | FLOOR LAYOUT INDICATES THAT SEPARATE | | | STACKS SHOULD WORK. | | | D) MAXIMUM DFU ON 2" WET VENT IS 4 PER | | | TABLE 909.3. MASTER BATH SHOWS 6 DFU'S | | | ON 2" IN BOTH MASTER BATHS. | | | E) LAVS ARE ON SEPARATE WALLS IN MASTER | | | BATHS AND REQUIRE SEPARATE STACKS FOR | | | EACH. MAXIMUM 5' FROM TRAP TO VENT PER | | | TABLE 906.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|