| 2004-05-07 00:00:00 | DENIED: |
| | 1.ONLY ONE SET OF MECHANICAL PLANS |
| | SUBMITTED FOR REVIEW.PER 2001 FBC(M) |
| | 104.2.1, PROVIDE TWO OR MORE COPIES OF |
| | PLANS AND SPECIFICATIONS. |
| | |
| | 2.PLANS INDICATE O.A. CALCULATIONS |
| | PER 2001 FBC(M) 402.2, PROVIDE |
| | CALCULATIONS ON PLAN. |
| | |
| | 3.1ST FLOOR "SANTA BARBARA", SOME OF |
| | THE DUCTS ARE NOT SIZED.INDICATE IF |
| | THEY ARE "TYPICAL". |
| | |
| | 4."SANTA BARBARA" DOES NOT INDICATE |
| | RETURN AIR TO ROOMS SEPARATED BY DOORS. |
| | SHOW COMPLIANCE WITH REVISED 2001 |
| | FBC(M) 601.4.PLEASE NOTE, ALL RETURN |
| | AIR INTO THE MASTER SUITE IS TO BE |
| | INCLUDED IN THE CALCULATION FOR A |
| | "TOTAL" OF SUPPLY AIR TO THAT SPACE. |
| | |
| | 5.AC NOTES INDICATE AUXILIARY DRAIN |
| | PAN WITH FLOAT SWITCH FOR THE 2ND FLOOR |
| | UNITS ONLY.THIS IS INCORRECT, PER |
| | 2001 FBC(M) 307.2.3, ALL COILS ARE TO |
| | HAVE PROTECTION. |
| | |
| | 6.1ST FLOOR DRYER EXHAUST INDICATES |
| | VENT TO ROOF.PLANS DO NOT INDICATE |
| | WHAT TYPE OF DUCT WILL BE USED FOR THE |
| | DRYER EXHAUST.PROVIDE UL LISTING AND |
| | DETAIL FOR THE PENETRATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |