Plan Review Notes
Plan Review Notes For Permit 04041627
Permit Number 04041627
Review Stop B
Sequence Number 1
Notes
Date Text
2004-05-21 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) REVISE PLAN NOTE 10 ON C1. IMPACT
 PROTECTION IS REQUIRED IN WIND BORNE
 DEBRIS REGIONS PER FBC 1606.1.4.
  
 4) SPECIFY THAT THE DOORS FROM THE
 GARAGE TO THE HABITABLE SPACE ARE
 REQUIRED TO BE 3/4 HOUR FIRE RATED DOORS
 WITH CLOSERS. SEE FBC 705.1.3.
  
 5) THE WALLS BETWEEN THE GARAGES AND THE
 HABITABLE SPACE ARE REQUIRED TO BE ONE
 HOUR FIRE RATED PER FBC 411.2.6 AND 704.
  
 6) THE WALLS BETWEEN THE GARAGES AND
 CONDITIONED SPACE ARE REQUIRED TO BE
 INSULATED PER FBC CHAPTER 13.
  
 7) SHOW COMPLIANCE WITH FAIR HOUSING ACT
 DESIGN MANUAL. SHOW MINIMUM CLEAR FLOOR
 SPACE AT TOILET OF 48"X56". CENTER OF
 TOILET TO BE 18" OFF WALL. SEE FHADM
 PAGE 7.43.
  
 8) ALL DOORS THAT A PERSON MUST PASS
 THROUGH (SUCH AS WALK IN CLOSETS, BATHS,
 ETC.) MUST MEET THE REQUIREMENTS FOR
 "USEABLE" DOORS AND PROVIDE A 32"NOMINAL
 CLEAR OPENING. A 2'-10" DOOR IS REQUIRED
 SEE FHADM PG. 3.5.
  
 9) THE GROUND FLOOR AND SECOND FLOOR
 GROSS AREA CALCS. ARE INCORRECT. PLEASE
 CORRECT.
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 11) SPECIFY THE TRUSS BOTTOM CORD LIVE
 LOAD ON THE PLANS. SEE FBC TABLE 1604.1.
  
 12) SUBMIT KEY PLANS AND INSTALLATION
 SCHEDULES FOR THE STORM PANELS.
  
 13) THE MISSLE IMPACT PROTECTION
 INSTALLATION PLAN NEEDS TO BE SIGNED AND
 NOTARIZED. IT MUST ALSO BE APPROVED BY
 THE BUILDING OFFICIAL.
  
 14) SUBMIT ENGINEERING FOR THE BALCONY
 GUARD RAILS.
  
 15) SUBMIT COMPLIANCE LETTER FROM PALM
 BEACH LIFTS.
  
 16) PLEASE SUBMIT TWO COPIES OF ALL
 ITEMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714