| Plan Review Notes For Permit 04041550 |
| Permit Number |
04041550 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-13 00:00:00 | BUILDING REVIEW PROVISO: | | | 1-REVISE/CLARIFY SURVEY: THERE ARE TWO | | | NORTH ARROWS POINTING TO OPPOSITE | | | DIRECTIONS. REVISE SURVEY SHOWING | | | CORRECT NORTH ARROW ORIENTATION. | | | 2-DETAIL E/4 AND RESIDENTIAL NOTES ON | | | SHEET #2 DON'T MATCH. CLARIFY FASTENER | | | SPACING. SEC. 104.2.1.2 CITY AMENDMENT | | | TO FBC 2001. | | | 3-SECTION A/4: SPECIFY WHERE ARE TABLES | | | 6 AND 8 FOR ROOF TILE FASTENERS TAKEN | | | FROM. SEC. 104.2.1.1 CITY AMENDMENTS | | | TO FBC 2001. | | | 4-FLOOD ZONE AO: NEED TO PROVIDE THE | | | ELEVATION CERTIFICATE. | | | 5-GARAGE DOORS: DWGS SUBMITTED DON'T | | | MATCH THE DWGS SUBMITTED ONSBCCI | | | EVALUATION REPORT. THE DATE DWGS WERE | | | SIGNED AND SELAED IS NOT THE SAME. | | | PROVIDE COPIES OF DWGS THAT WERE | | | SUBMITTED TO SBCCI. |
|