2004-04-28 00:00:00************DENIED**********************
 1) UNDER SEQUENCE OF OPERATION NOTE #3
 ACTIVATION OF ANY DUCT MOUNTED SMOKE
 DETECTORS SHALL ACTIVATE FULL GENERAL
 ALARM NOT A SUPERVISORY IN THE CITY OF
 WEST PALM BEACH,(PER FIRE MARSHAL).
  
 2) FIRE ALARM SYSTEM SHALL BE CLASS"A"
 OR FULLY ADDRESSABLE.
  
 3) SOME DEVICES ARE DRAWN IN ON THE PLAN
 WITH ? BY THEM. WHAT DOES THIS MEAN.
  
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910