2004-05-03 00:00:00PROVISO:
 1.EXHAUST OUTLETS SHALL BE A MINIMUM
 OF 10 FT HORIZONTALLY FROM ADJACENT
 PROPERTY LINES OR FROM PARTS OF THE
 SAME OR CONTIGUOUS BUILDING. 2001
 FBC(M) 506.3.14.3.
  
 2.PLEASE NOTE, AIR VELOCITY WITHIN THE
 DUCT SHALL BE NOT LESS THAN 1,500 FPM &
 NOT GREATER THAN 2,500 FPM.
  
 3.PROVIDE MANUFACTURER INSTALLATION
 DATA FOR THE 3M FASTWRAP+ THATIS
 INDICATED ON THE PLAN.
  
 4.ALL WELDS TO BE INSPECTED PRIOR TO
 COVERING.