| Plan Review Notes For Permit 04041460 |
| Permit Number |
04041460 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-03 00:00:00 | PROVISO: | | | 1.EXHAUST OUTLETS SHALL BE A MINIMUM | | | OF 10 FT HORIZONTALLY FROM ADJACENT | | | PROPERTY LINES OR FROM PARTS OF THE | | | SAME OR CONTIGUOUS BUILDING. 2001 | | | FBC(M) 506.3.14.3. | | | | | | 2.PLEASE NOTE, AIR VELOCITY WITHIN THE | | | DUCT SHALL BE NOT LESS THAN 1,500 FPM & | | | NOT GREATER THAN 2,500 FPM. | | | | | | 3.PROVIDE MANUFACTURER INSTALLATION | | | DATA FOR THE 3M FASTWRAP+ THATIS | | | INDICATED ON THE PLAN. | | | | | | 4.ALL WELDS TO BE INSPECTED PRIOR TO | | | COVERING. |
|