| Plan Review Notes For Permit 04041411 |
| Permit Number |
04041411 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-05-12 00:00:00 | *** PROVISO ** | | | | | | ALL REVISIONS TO BE SUBMITTED FOR | | | REVIEW | | | BEFORE ROUGH. | | | | | | 1 )NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY | | | NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | DUE TO THE ACTUAL UNKNOWN FIXTURES | | | BEING | | | INSTALLED AT THIS TIME. PLEASE SUBMIT | | | REVISED BEFORE ROUGH.. | | | | | | 2)NOTE: PLEASE SEE 210.52 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|