| Date |
Text |
| 2006-06-16 00:00:00 | ******* UNSAT 2ND REVIEW OF REVSION *** |
| | |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW |
| | AND THIS REVIEW. |
| | |
| | 1) NOTE: NOTE #1 NO, PLEASE SEE NUMEROUS |
| | ITEMS ARE STILL NOT CORRECT. PLEASE SEE |
| | LOADS EXCEEDING BRKR OCP, BLANK SPACES |
| | WITH LOADS, 50A BRKRS ON 1HP PUMPS, SEE |
| | PANEL "B" NOW SHOWS 24 AND 72 A'S ON TOW |
| | SEPARATE PHASES, #1'S ON RISER FOR |
| | FEEDERS, #6'S ON PANEL SCHEDULE ETC ETC. |
| | PLEASE SE MOST OF THESE ARE REDLINED ON |
| | PLANS. |
| | 215.5,240.4,240.6,310.16, ETC |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE CORRELATE PANEL "B" |
| | LOADS, SIZE ETC. PLEASE SEE RISER SHOWS |
| | THIS AS 50A MLO, YET PANEL IS SHOWN AS |
| | 100A MLO. |
| | PLEASE SEE LOAD ON PANEL "A" IS SHOWN AT |
| | 72A'S WHICH FAR EXCEEDS THAT OF A 50A |
| | BRKR. |
| | 240.4,310.16,215.5 |
| | |
| | 2) NOTE:NOTE #2 NO, SAME NOTE AND SAME |
| | AS NOTE #1. |
| | PLEASE SEE WATER HEATER IS NOW REMOVED |
| | FROM PANEL SCHEDULE YET LOAD IS STILL |
| | BEING SHOWN IN A BLANK SPACE?? |
| | PLEASE STILL INDICATE ON SCHEDULE, |
| | HOWEVER IF IT IS GAS, THEN THERE IS NO |
| | LOAD. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE CORRLEATE ALLLOADS AND |
| | ITEMS ON LOAD CALCULATIONS WITH THOSE ON |
| | PANEL SCHEDULES. |
| | PLEASE SEE THE MICRO/OVEN IS HSOWN WITH |
| | 40A LOAD ON SCHEDULE, YET CALCS ONLY |
| | SHOW THIS AS 1.5KW?? |
| | 215.5 |
| | PLEASE SEE COOKTOP WITH A HIGH LOAD, ON |
| | A 1-20A BRKR, YET CALCS SHOWS LOAD AT |
| | 8KW. CORRELATE OCP, AWG AND LOADS. |
| | LABEL ACCORDINGLY. |
| | PLEASE SEE A GAS RANGE IS SHOWN ON LOAD |
| | CALCS. |
| | PLEASE SE WATER HEATER IS SHOWN AS GAS |
| | ON PANEL SCHEDULE, YET LOAD ON SCHEDULE |
| | DOES NOT CORRELATE WIHT THIS NOR DOES |
| | THE CALCULATIONS. |
| | 215.5 |
| | |
| | 3) NOTE: NOTE #3, NO, PLEASE SEE |
| | DEN/STUDY WHICH STILL REQUIRES SOME SORT |
| | OF LT FIXTURE. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE REDLINED LOCATIONS |
| | FOR A MIN LT FIXTURE OF SOME TYPE WILL |
| | BE REQUIRED FOR EGRESS. NFPA-101, 7.8, |
| | NFPA-70 210.70, NFPA-101 CHAPTER 24 |
| | |
| | 4) NOTE: OK. |
| | |
| | |
| | 5) NOTE:NOTE #5 NO, |
| | |
| | |
| | **PREVIOUS NOTE ** |
| | PLEASE SEE ALL LIGHTING AND |
| | RECEPT CIRCUITS ON PANEL SCHEDULE SHALL |
| | BE SPECIFIC TO ROOM/AREA/LOCATION AND |
| | PURPOSE. |
| | PLEASE KNOW, IT IS NOT ACCEPTABLE TO |
| | JUST LIST ALL LIGHTING OR RECEPTS |
| | WITHOUT WHICH RM ETC THEY ARE FEEDING. |
| | IE; B-6 MASTER BDRM RECEPTS, FOYER LTS |
| | ETC. |
| | |
| | 6) NOTE:OK |
| | |
| | NEW NOTE: |
| | |
| | 7) NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) IS ATTACHED. IF PLANS COME |
| | BACK WITH ALL OF THESE ADDRESSED THE |
| | ABOVE SHALL BE IMPLEMENTED. |
| | PLEASE SEE THIS WILL BE THE 2ND SET |
| | RETAINED. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |