| 2005-11-16 00:00:00 | *********** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE NUMEROUS RECEPTS |
| | MISSING PER 210.52. |
| | |
| | 2)NOTE: PLEASE SEE 210.8A6, WHICH |
| | REQUIRES ALL RECEPTS SERVING KITCHEN |
| | COUNTERSPACE TO BE GFI/GFI PROTECTED. |
| | |
| | 3)NOTE: PLEASE SEE ALL OTHER RECEPTS |
| | LOCATED WITHIN 6' OF OTHER SINLS OR |
| | WETBAR LOCATIONS SHALL ALSO BE GFI/GFI |
| | PROTECTED. |
| | 210.8A7 |
| | |
| | 4)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52H? |
| | |
| | 5)NOTE: PLEASE SEE MISSING GFI RECEPTS |
| | ALONG KITCHEN COUNTERSPACE, ISLAND ETC. |
| | 210.52C1-C5 |
| | |
| | 6)NOTE: PLEASE SEE CLARIFY RISER DIAGRAM |
| | GROUNDING ELECTRODE SYSTEM FROM MAIN |
| | DISCONNECT AND THEN ALSO SHOWS A |
| | GROUNDING ELECTRODE OF A "STEEL PIPE"?? |
| | FROM METER. |
| | PLEASE SEE 250.50, 250.6 AND 250.24 FOR |
| | LOCATION OF GROUNDING ELECTRODE |
| | CONDUCTOR, GROUNDING ELECTRODES ETC. |
| | PLEASE VERIFY FIELD INSTALLATION. |
| | |
| | 7)NOTE: PLEASE CORRELATE LOAD |
| | CALCULATIONS AND PANEL SCHEDULE FOR |
| | COOK-TOP, RANGE, AND OVENS. |
| | PLEASE SEE GAS, ELEC OR NOT SHOWN.?? |
| | |
| | 8)NOTE: PLEASE VERIFY 1HP PUMP WHICH |
| | SHOWS 40A OCP?? AND #8 AWG?? |
| | THIS DOES NOT SEEM TO BE CORRECT, PLEASE |
| | SEE 430 FOR MAX OCP AND CODE LTR AND |
| | TYPES OF MOTORS. |
| | |
| | 9)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | PLEASE REVISE LOAD CALCUALTIONS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |