| Plan Review Notes For Permit 04041341 |
| Permit Number |
04041341 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-02-17 00:00:00 | THIRD MECH. REVIEW: | | | | | | 1. RETURN AIR DUCT FROM BALLERY | | | REFLECTS 16" THEN CHANGES TO 10" DUCT | | | RETURNING TO A.H.U.#1 . | | | PLEASE CORRECT. | | | 2. RETURN AIR DUCT FROM BEDROOM #3 NOT | | | SIZED. | | | 3. RETURN AIR DUCT FROM BEDROOM #2 AND | | | #3 REFLECT 10" RETURNING TO A.H.U.#1. | | | | | | PLEASE CORRECT R/A DUCT SIZE. | | | | | | 4. AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIED PER 2001 FBC/M | | | 307.2.3 FOR A.H.U. . | | | | | | PAT RAFTER 561/805/6728 . PLEASE CALL | | | IF THEAR ENY QUESTION. | | | |
|