| Plan Review Notes For Permit 04041341 |
| Permit Number |
04041341 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-02-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT P-2 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, DOES NOT | | | MEET CODE REQUIREMENTS, NOR IS IT DRAWN | | | IN A CLEAR ISOMETRIC FORM. | | | A) SEE EXAMPLE ON SHT P-2 IN RED INK | | | THAT SHOWS PIPING THAT IS DRAWN IN THE | | | VERTICLE INDICATES PIPING TO A SECOND | | | FLOOR. AND SEE EXAMPLE OF REMDEDY FOR | | | THE W/M, UTILITY SINK. | | | B) ISOMETRIC IS A REVERSE OF THE FLOOR | | | PLAN. SECTION 104.2.1. | | | C) BATH #3 IS MISSING THE TUB ON THE | | | SANT. RISER THAT IS SHOWN ON THE FLOOR | | | PLAN. SECTION 104.2.1. | | | D) UTILITY SINK IS NOT VENTED. SECTION | | | 901.2.1. | | | E) WASH MACHINE REQUIRES A MIN. 2' | | | STANDPIPE, AND A CLEANOUT 4' ABOVE THE | | | FLOOR. SECTIONS 1002.1 & 708.10. | | | F) TRAPS ARE REQUIRED ON ALL SHOWERS, | | | TUBS, AND BIDET. SECTION 1002.1. | | | G) THE AIR ADMITTENCE VALVE FOR THE | | | ISLAND SINK IN THE KITCHEN SHALL BE | | | SHOWN ON THE SANITARY RISER DIAGRA. | | | SECTION 104.2.1. & SECTION 901.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|