| 2006-07-03 00:00:00 | ******** UNSAT *********** |
| | |
| | 1) NOTE: PLEASE SEE NUMEROUS ITEMS ON |
| | PANEL SCHEDULE AND LOCD CALCULATIONS |
| | WHICH STILL DO NOT CORRELATE. |
| | PLEASE SEE AHU'S, SPA, POOL, DISHWASHER |
| | (S), LAUNDRY/WASHER, ETC ETC. |
| | PLEASE SEE PANELS STILL DO NOT |
| | CORRELATE. |
| | 215.5,240.4,310.16, ( 2002 NEC) |
| | |
| | 2) NOTE: PLEASE SHOW EACH PANEL WITH |
| | CORRECT LOADS AND LOAD CALCULATIONS PER |
| | NEC 220. |
| | PLEASE SEE THE LOADS FOR "B". |
| | |
| | 3) NOTE: PLEASE SEE MIN LT FIX REQUIRED |
| | FOR EGRESS. LS 101 7.8, 210.70 |
| | |
| | 4) NOTE: PLEASE SEE THAT THE RISER AND |
| | PANELS STILL DO NOT CORRELATE. |
| | LOADS DO NOT CORRELATE. |
| | 215.5,310.16,240.4 ETC. |
| | |
| | *** IMPORTANT *** |
| | |
| | 4) NOTE: PLEASE KNOW, ONE OF THE COPIES |
| | ARE RETAINED ONCE AGAIN. IF PLANS DO NOT |
| | COME BACK WITH ALL CORRECTIONS AS NOTED |
| | ON ALL PREVIOUS REVIEWS, A 4X FEE FOR |
| | THE PLAN REVIEW PORTION OF THE PERMIT |
| | FEE WILL BE ASSESSED AS REQUIRED PER FS |
| | 553.80(2)(B) TO THE DESIGN PROFESSIONAL. |
| | PLEASE KNOW ALL PLANS RETAINED TO DATE |
| | WILL BE TURNED OVER THE STATE'S LEGAL |
| | COUNSEL TO THE FLORIDA BOARD OF |
| | ARCHITECT'S FOR PEIR REVIEW. PLEASE SEE |
| | FS 481.221(4) |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |