| Plan Review Notes For Permit 04041317 |
| Permit Number |
04041317 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-08-30 00:00:00 | ********** UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE PLANS HAVE BEEN | | | REVISED WITH "WHITE-OUT" ANDHAND=DRAWN | | | CHANGES. PLEASE SEE THAT ALL CHANGES ARE | | | DONE BY ARCHITECT, REPRINTED AND SIGNED, | | | DATED AND SEALED. FS 481.221 | | | | | | 2)NOTE: PLEASE SEE SOME COMMENTS FROM | | | PREVIOUS REVIEW STILL NEED TO BE | | | ADDRESSED. | | | INFORMATION IN TITLE BLOCK. | | | GFI RECEPTS PER 210.8 | | | | | | | | | 3)NOTE: PLEASE SEE RISER DIAGRAM HAS NOW | | | BEEN REVISED, HOWEVER PLANS STILL SHOW A | | | | | | MAIN OUTSIDE? | | | PLEASE ALSO SEE PANELS ARE BEING SHOWN | | | AS BEING FED OVERHEAD.?? | | | PLEASE SEE 230.70, NO MORE THAN 8' OF | | | UNPROTECTED CONDUCTOR MAY BE "INSIDE" | | | HOUSE. | | | PLEASE PROVIDE MAINS AND OVERCURRENT | | | PROTECTION OUTSIDE IF INDEED SERVICE IS | | | BEING FED OVERHEAD TO PANELS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|