Plan Review Notes
Plan Review Notes For Permit 04041317
Permit Number 04041317
Review Stop E
Sequence Number 5
Notes
Date Text
2005-08-30 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE PLANS HAVE BEEN
 REVISED WITH "WHITE-OUT" ANDHAND=DRAWN
 CHANGES. PLEASE SEE THAT ALL CHANGES ARE
 DONE BY ARCHITECT, REPRINTED AND SIGNED,
 DATED AND SEALED. FS 481.221
  
 2)NOTE: PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
 INFORMATION IN TITLE BLOCK.
 GFI RECEPTS PER 210.8
  
  
 3)NOTE: PLEASE SEE RISER DIAGRAM HAS NOW
 BEEN REVISED, HOWEVER PLANS STILL SHOW A
  
 MAIN OUTSIDE?
 PLEASE ALSO SEE PANELS ARE BEING SHOWN
 AS BEING FED OVERHEAD.??
 PLEASE SEE 230.70, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTOR MAY BE "INSIDE"
 HOUSE.
 PLEASE PROVIDE MAINS AND OVERCURRENT
 PROTECTION OUTSIDE IF INDEED SERVICE IS
 BEING FED OVERHEAD TO PANELS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  