| 2005-08-04 00:00:00 | *********** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE 250.6,250.24 |
| | "EQUIPMENT GROUNDING" CONDUCTORS ARE NOT |
| | INSTALLED FROM METER TO THE FIRST MEANS |
| | OF DISCONNECT. |
| | PLEASE SEE THIS WAS NOTED ON ALL THREE |
| | PREVIOUS REVIEWS AND THIS IS STILL |
| | SHOWN. |
| | PLEASE SEE THE "EQUIPMENT GROUNDING" |
| | CONDUCTORS ARE MISSING FROM MIANS OT |
| | SUB-PANELS. |
| | 250.110,250.24 SIZED PER 250.122 |
| | |
| | 2)NOTE: PLEASE SEE MISSING KITCHEN |
| | COUNTERSPACE GFI. COUNTERSPACE SHOWN IS |
| | MORE THAN 4'. 210.52C1 |
| | |
| | 3)NOTE: PLEASE SEE POOL SUB PANEL "C" IS |
| | NOT SHOWN ON PLANS? |
| | PLEASE ALSO CORRELATE PLANS AND RISER. |
| | PLANS ONLY INDICATEONE MAIN? |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE POOL SUB PANEL IS |
| | SHOWN AS A 200A PANEL WITH A 80A FEED. |
| | PLEASE VERIFY IF INDEED PANEL INSTALLED |
| | IS A 42 CIRCUIT 200A RATED PANEL? |
| | PLEASE SEE RISER DIAGRAM SHOWS 8/0'S FOR |
| | FEEDERS AND A #2 EQUIPMENT GROUNDING |
| | CONDUCTOR? |
| | PLEASE SEE 8/0 IS NOT A WIRE SIZE, ETC |
| | 240.4,310.16 |
| | PLEASE SEE AWG SHOWN ON PANEL "A" FOR |
| | POOL PANEL IS SHOWN AS #4. |
| | |
| | 5)NOTE: PLEASE CORRELATE LOAD SHOWN ON |
| | PANEL "A" FOR POOL SUB PANEL AND LOAD |
| | SHOWN ON POOL PANEL "C". |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SEE MISSING GFI RECEPT |
| | REQUIRED W/ IN 3' OF "HIS BATH' LAV. |
| | 210.52D |
| | |
| | 7)NOTE: PLEASE SEE FAC 61G1-16.004, |
| | TITLE BLOCK SHALL CONTAIN THE PRINTED |
| | ANME AND LICENSE # (AR) OF THE ARCHITECT |
| | OF RECORD. |
| | THIS WAS NOT ON NOTES FROM REVIEWS LAST |
| | YEAR. |
| | |
| | 8)NOTE: PLEASE SEE MANY ITMES ARE SHOWN |
| | AS OPTIONAL ON PLANS?PLEASE KNOW, IF |
| | THESE PLANS ARE FOR FINAL/CO, ALL ITEMS |
| | INSTALLED SHALL BE SHOWN, ALL ITMES NOT |
| | INSTALLED, SHALL BE DELETED. |
| | |
| | 9)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. PLEASE |
| | SHOW THIS LOAD IN ADDITION TO THE 3WATS |
| | PER SQ FT. PLEASE SEE THERE ARE OVER 80 |
| | RECESSED LTS. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |