Plan Review Notes
Plan Review Notes For Permit 04041317
Permit Number 04041317
Review Stop E
Sequence Number 3
Notes
Date Text
2004-06-17 00:00:00********** REDLINED ***********
  
 PLANS/RISER STILL SHOW EQUIPMENT GROUND-
 -ING CONDUCTORS BEING INSTALLED FROM
 METER TO DISCONNECTS.
 THIS WAS NOTED ON PREVIOUS TWO REVIEWS,
 AN EQUIPMENT GROUNDING CONDUCTOR IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT. 250.24,250.6
 PLANS HAVE BEEN REDLINED.
 RECEPT SHOWN FOR DINING RM FLR, NOT AN
 OPTION, REQ'D PER 210.52
 ALL REVISIONS/OPTS ARE TO BE REVIEWED
 BEFORE ROUGH.