| Plan Review Notes For Permit 04041317 |
| Permit Number |
04041317 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-06-17 00:00:00 | ********** REDLINED *********** | | | | | | PLANS/RISER STILL SHOW EQUIPMENT GROUND- | | | -ING CONDUCTORS BEING INSTALLED FROM | | | METER TO DISCONNECTS. | | | THIS WAS NOTED ON PREVIOUS TWO REVIEWS, | | | AN EQUIPMENT GROUNDING CONDUCTOR IS ONLY | | | INSTALLED AFTER THE FIRST MEANS OF | | | DISCONNECT. 250.24,250.6 | | | PLANS HAVE BEEN REDLINED. | | | RECEPT SHOWN FOR DINING RM FLR, NOT AN | | | OPTION, REQ'D PER 210.52 | | | ALL REVISIONS/OPTS ARE TO BE REVIEWED | | | BEFORE ROUGH. |
|