Date Text
2004-05-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS.
 A) LAUNDRY SINK AND WASH MACHINE SHALL
 NOT CONNECT TO THE STACK ON A DOUBLE
 SANITARY TEE. SECTION 706.3. CONNECT THE
 WASH MACHINE LOWER ON THE STACK THAN THE
 LAUNDRY SINK.
 B) CLEAN OUT REQUIRED 4' ABOVE THE
 FLOOR AT WASH MACHINE. SECTION 708.10
 C) TUB NOT VENTED IN BATH #2. SECTION
 901.2.1
 D) LAV ON RIGHT SIDE OF WATER CLOSET IN
 POWDER ROOM.
 E) BAR SINK NOT SHOWN ON FLOOR PLAN.
 SECTION 104.2.1
 F) SEE RED LINE CORRECTIONS ON RISER
 DIAGRAM. MAKE CORRECTIONS AND RESUBMIT
 FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692