| Plan Review Notes For Permit 04041317 |
| Permit Number |
04041317 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A-1 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | | MEET CODE REQUIREMENTS. | | | A) LAUNDRY SINK AND WASH MACHINE SHALL | | | NOT CONNECT TO THE STACK ON A DOUBLE | | | SANITARY TEE. SECTION 706.3. CONNECT THE | | | WASH MACHINE LOWER ON THE STACK THAN THE | | | LAUNDRY SINK. | | | B) CLEAN OUT REQUIRED 4' ABOVE THE | | | FLOOR AT WASH MACHINE. SECTION 708.10 | | | C) TUB NOT VENTED IN BATH #2. SECTION | | | 901.2.1 | | | D) LAV ON RIGHT SIDE OF WATER CLOSET IN | | | POWDER ROOM. | | | E) BAR SINK NOT SHOWN ON FLOOR PLAN. | | | SECTION 104.2.1 | | | F) SEE RED LINE CORRECTIONS ON RISER | | | DIAGRAM. MAKE CORRECTIONS AND RESUBMIT | | | FOR REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|