| 2004-05-07 00:00:00 | ************* UNSAT *************** |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER W/ |
| | PANELS. PANELS ARE SHOWN AS MCB AND |
| | RISER SHOWS MLO? |
| | |
| | 2)NOTE: PLEASE VERIFY 150A PANELS ARE |
| | SHOWN AS 42 CIRCUIT? |
| | |
| | 3)NOTE: RISER SHOWS EQUIPMENT GROUNDING |
| | CONDUCTORS BEING INSTALLED BETWEEN METER |
| | AND MAINS/FIRST MEANS IF DISC. |
| | PLEASE SEE 250.6, 250.24. THIS IS NOT |
| | PERMITTED. ONLY AFTER THE FIRST MEANS OF |
| | DISC. |
| | |
| | 4)NOTE:PLEASE SEE 210.52, 210.52C1 FOR |
| | RECEPT SPACING IN TWO RMS AND KITCHEN |
| | COUNTER/ DESK AREA. |
| | |
| | 5)NOTE: PLEASE PROVIDE ROOM DISIGNATION |
| | ON PLANS. |
| | |
| | 6)NOTE: PLEASE SEE AHU#3, SHOWS 8KW |
| | W/ 30A OCP. PLEASE SEE 424.3B, MIN OCP |
| | FOR HEAT 125% OF KW RATING. |
| | |
| | 7)NOTE: PLEASE SEE FOYER IS SHOWN AS |
| | HAVING A J-BOX. A LT FIXTURE OF SOME |
| | SORT WILL BE REQ'D FOR EGRESS LT, 210.70 |
| | LS 101 5-8 |
| | |
| | 8)NOTE: PLEASE SEE THAT SD IN MASTER |
| | BEDROOM AREA MUST BE MOVED INTO MASTER |
| | BEDRM. PLEASE SEE NFPA-72 FOR INSTALLA- |
| | -TION LOCATIONS. 8-1.4.2, 8-1 |
| | |
| | 9)NOTE: PLEASE SEE FS 481.221, WHEN PLAN |
| | -S A RE SIGNED BY THE ARCH, THEY MUST |
| | ALSO BE DATED BY ARCH. |
| | |
| | PLEASE ALSO SEE BLDG REVIEW COMMENTS |
| | FOR POSSIBLE BLDG VALUATION ADJUSTMENT. |
| | FBC 104.6.5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |