| Plan Review Notes For Permit 04041316 |
| Permit Number |
04041316 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-26 00:00:00 | DENIED: | | | INSUFFICIENT INFORMATION, PLEASE PROVIDE | | | THE FOLLOWING INFORMATION FOR COMPLIANCE | | | WITH NFPA 33: | | | | | | 1.INDICATE THE UTILIZATION OF THE | | | SPRAY BOOTH.(AUTO, FURNITURE, ETC?) | | | | | | 2.INDICATE CLEARANCE AROUND SPRAY | | | BOOTH. | | | | | | 3.PROVIDE DISTANCE FROM EXHAUST | | | TERMINATION TO THE PROPERTY LINES & | | | FRESH AIR INTAKES. | | | | | | 4.INDICATE FRESH AIR MAKE UP. | | | | | | 5.INDICATE STORAGE FOR COMBUSTIBLES. | | | | | | 6.PROVIDE SPECIFICATION ON THE EXHAUST | | | FAN(S). | | | | | | SHOW COMPLIANCE WITH NFPA 33 AND 34 IF | | | APPLICABLE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|