Plan Review Notes
Plan Review Notes For Permit 04041280
Permit Number 04041280
Review Stop E
Sequence Number 3
Notes
Date Text
2005-02-28 00:00:00**** UNSAT ****
  
 PLEASE SEE THERE ARE MANY ITEMS ON PANEL
 SCHEDULES WHICH NEED TO CORRELATE OCP/KW
 LOAD AND AWG.
  
 1)NOTE: PLEASE SEE MIN #12 20A FOR BATH
 GFI RECEPT. 210.11C3, 210.52D
  
 2)NOTE: PLEASE SEE MAX KW RATING FOR A
 20A CIRCUIT IS 1920W'S.
 PLEASE ALSO SEE 5KW FOR DRYER SHOWN ON A
 1-P 20A CIRCUIT?
 PLEASE SEE 6KW FOR COOK-TOP ON A 1P-20A
 BRKR?
  
 3)NOTE: PLEASE SEE POOL PANEL LOAD SHOWN
 AT 5.2 KW , HOWEVER PANEL "B" INDICATES
 LOAD AS 6.8 KW.
  
 4)NOTE: PLEASE SEE PLANS INDICATES TWO
 MAIN DISC'S ON THE OUTSIDE OF HOUSE,
 HOWEVER RISER DOES NOT SHOW THIS.
  
 PLEASE SEE ONE SET OF PLANS HAVE BEEN
 REDLINED FOR THE ABOVE COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]