| Plan Review Notes For Permit 04041280 |
| Permit Number |
04041280 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-02-28 00:00:00 | **** UNSAT **** | | | | | | PLEASE SEE THERE ARE MANY ITEMS ON PANEL | | | SCHEDULES WHICH NEED TO CORRELATE OCP/KW | | | LOAD AND AWG. | | | | | | 1)NOTE: PLEASE SEE MIN #12 20A FOR BATH | | | GFI RECEPT. 210.11C3, 210.52D | | | | | | 2)NOTE: PLEASE SEE MAX KW RATING FOR A | | | 20A CIRCUIT IS 1920W'S. | | | PLEASE ALSO SEE 5KW FOR DRYER SHOWN ON A | | | 1-P 20A CIRCUIT? | | | PLEASE SEE 6KW FOR COOK-TOP ON A 1P-20A | | | BRKR? | | | | | | 3)NOTE: PLEASE SEE POOL PANEL LOAD SHOWN | | | AT 5.2 KW , HOWEVER PANEL "B" INDICATES | | | LOAD AS 6.8 KW. | | | | | | 4)NOTE: PLEASE SEE PLANS INDICATES TWO | | | MAIN DISC'S ON THE OUTSIDE OF HOUSE, | | | HOWEVER RISER DOES NOT SHOW THIS. | | | | | | PLEASE SEE ONE SET OF PLANS HAVE BEEN | | | REDLINED FOR THE ABOVE COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|