Plan Review Notes
Plan Review Notes For Permit 04041257
Permit Number 04041257
Review Stop B
Sequence Number 1
Notes
Date Text
2004-05-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04041257
 ADD: 2600 N FLAGLER# 509
 CONT: MICHAEL RUFINO
 TEL: (561)236-2800
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) DEFINITIONS: FL S S 489.105
 BUILDING CONTRACTOR:(B) MEANS A CONTRACT
 OR WHOSE SERVICES ARE LIMITED TO CON-
 STRUCTION OF COMMERCIAL BUILDINGS AND
 SINGLE-DWELLING OR MULTIPLE-DWELLING
 RESIDENTIAL BUILDINGS, WHICH COMMERCIAL
 OR RESIDENTIAL BUILDINGS DO NOT EXCEED
 3 STORIES IN HEIGHT, AND ACCESSORY USE
 STRUCTURES IN CONNECTION THEREWITH OR A
 CONTRACTOR WHOSE SERVICES ARE LIMITED TO
 REMODELING, REPAIRING, OR IMPROVEMENT OF
 ANY SIZE BUILDING IF THE SERVICES DO NOT
 AFFECT THE STRUCTURAL MEMBERS OF THE
 BUILDING.
 THE REPLACEMENT OF EXTERIOR WINDOWS
 AND DOORS IS CONSIDERED AS PART OF THE
 STRUCTURAL ENVELOPE OF THE BUILDING.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SLIDING GLASS DOORS/ W LARGE MISSLE
 IMPACT TESTING.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3) ADDITIONAL INFORMATION REQUIRED,
 PLANS INDICATE THE USE OF CROWN AND BASE
 WHAT TYPE OF MATERIAL?
 FOAM PLASTIC TRIM 803.4
 FOAM PLASTICS SHALL NOT BE USED AS INTER
 IOR FINISHES.
 EXCEPTION: FOAM PLASTIC TRIM, DEFINED AS
 PICTURE MOLDS, CHAIR RAIL, BASEBOARDS,
 HANDRAILS CEILING BEAMS, DOOR TRIM AND
 WINDOW TRIM, OR CROWN MOLDING SHALL BE
 PERMITTED PROVIDED:
 1) THE MINIMUM DENSITY IS 20 LB/CU FT.
 2) THE MAXIMUM THICKNESS IS 1/2" AND
 THE MAXIMUM WIDTH IS 4".
 3) THE TRIM CONSTITUTES NO MORE THAN
 10% OF THE AREA OF WALL OR CEILING.
 4) THE FLAMESPREAD RATING DOES NOT
 EXCEED 75 WHEN TESTED PER ASTM E 84. THE
 SMOKE DEVELOPMENT RATING IS NOT LIMITED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026