| 2004-05-14 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04041257 |
| | ADD: 2600 N FLAGLER# 509 |
| | CONT: MICHAEL RUFINO |
| | TEL: (561)236-2800 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) DEFINITIONS: FL S S 489.105 |
| | BUILDING CONTRACTOR:(B) MEANS A CONTRACT |
| | OR WHOSE SERVICES ARE LIMITED TO CON- |
| | STRUCTION OF COMMERCIAL BUILDINGS AND |
| | SINGLE-DWELLING OR MULTIPLE-DWELLING |
| | RESIDENTIAL BUILDINGS, WHICH COMMERCIAL |
| | OR RESIDENTIAL BUILDINGS DO NOT EXCEED |
| | 3 STORIES IN HEIGHT, AND ACCESSORY USE |
| | STRUCTURES IN CONNECTION THEREWITH OR A |
| | CONTRACTOR WHOSE SERVICES ARE LIMITED TO |
| | REMODELING, REPAIRING, OR IMPROVEMENT OF |
| | ANY SIZE BUILDING IF THE SERVICES DO NOT |
| | AFFECT THE STRUCTURAL MEMBERS OF THE |
| | BUILDING. |
| | THE REPLACEMENT OF EXTERIOR WINDOWS |
| | AND DOORS IS CONSIDERED AS PART OF THE |
| | STRUCTURAL ENVELOPE OF THE BUILDING. |
| | |
| | 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) SLIDING GLASS DOORS/ W LARGE MISSLE |
| | IMPACT TESTING. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 3) ADDITIONAL INFORMATION REQUIRED, |
| | PLANS INDICATE THE USE OF CROWN AND BASE |
| | WHAT TYPE OF MATERIAL? |
| | FOAM PLASTIC TRIM 803.4 |
| | FOAM PLASTICS SHALL NOT BE USED AS INTER |
| | IOR FINISHES. |
| | EXCEPTION: FOAM PLASTIC TRIM, DEFINED AS |
| | PICTURE MOLDS, CHAIR RAIL, BASEBOARDS, |
| | HANDRAILS CEILING BEAMS, DOOR TRIM AND |
| | WINDOW TRIM, OR CROWN MOLDING SHALL BE |
| | PERMITTED PROVIDED: |
| | 1) THE MINIMUM DENSITY IS 20 LB/CU FT. |
| | 2) THE MAXIMUM THICKNESS IS 1/2" AND |
| | THE MAXIMUM WIDTH IS 4". |
| | 3) THE TRIM CONSTITUTES NO MORE THAN |
| | 10% OF THE AREA OF WALL OR CEILING. |
| | 4) THE FLAMESPREAD RATING DOES NOT |
| | EXCEED 75 WHEN TESTED PER ASTM E 84. THE |
| | SMOKE DEVELOPMENT RATING IS NOT LIMITED. |
| | |