| 2004-04-28 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) NEW TOILET ROOM SHALL COMPLY WITH |
| | SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND |
| | ALL SUBSECTIONS. SUBMIT A DETAIL SHOWING |
| | CLEAR FLOOR SPACE FOR W/C AND LAV, 5' |
| | TURNING AREA, HEIGHT OF W/C, MEASUREMENT |
| | OF WATER CLOSET AND LAV OFF WALL TO THE |
| | CENTERLINE OF FIXTURES, HEIGHT OF LAV., |
| | GRAB BAR HEIGHT/LENGTH ECT. |
| | 2) SINK IN RECEPTIONIST AREA SHALL COMPY |
| | WITH 11-4.24 AND ALL SUBSECTIONS. PROVI- |
| | DE A DETAIL SHOWING ALL REQUIREMENTS. |
| | 3) SHT 5 OF 5 SANITARY RISER DIAGRAM |
| | DOES NOT MEET CODE REQUIREMENTS. SECTION |
| | 909.1 ONLY THE FIXTURES WITHIN THE TOIL- |
| | ET ROOM SHALL DRAIN THROUGH THE WET VENT |
| | HORIZONTAL DRAIN. ALL OTHER FIXTURES |
| | SHALL DISCHARGE DOWNSTREAM OF THE WET |
| | VENTED TOILET ROOM FIXTURES. - D/TABLE |
| | NOT VENTED. |
| | 4) MORE INFORMATION REQUIRED FOR D/TABLE |
| | PLEASE SUBMIT MANUF. INFORMATION FOR |
| | THIS FIXTURE. SHOW APPROVAL BY AN APPRO- |
| | VED TESTING AGENCY PER SECTION 303.2 & |
| | 303.4 |
| | 5) SHT 5 OF 5 PLUMBING RISER DIAGRAM, |
| | MORE INFORMATION REQUIRED ON FIXTURE |
| | SHOWN AFTER MASSAGE ROOM SINK. THIS FIX- |
| | TURE IS NOT SHOWN ON FLOOR PLAN. PLEASE |
| | CALRIFY. SECTION 104.2.1 |
| | 6) A WATER RISER DIAGRAM IS REQUIRED PER |
| | SECTION 104.3.1.1. INDICATE ALL WATER |
| | HAMMER ARRESTORS REQUIRED BY SECTION |
| | 604.9 TO BE LOCATED NEAR THE FIXTURE AS |
| | REQUIRED IN PDI-WH 201 AND MANUF. INSTA- |
| | LLATION INSTRUCTIONS. |
| | 7) AN RPZ BACKFLOW IS REQUIRED ON WATER |
| | SERVICE. |
| | |
| | REVIEW BY KEN STEVENS |