| Date |
Text |
| 2005-06-14 00:00:00 | ************* UNSAT **************** |
| | |
| | PLEASE SEE THE FOLLOWING NOTES FOR THE |
| | GENERATOR WHICH CAME IN AS A REVISIONS |
| | UNDER THE MAIN BLDG PERMIT.. |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT FOR SEPARATE |
| | GENERATOR PERMIT. |
| | PLEASE SUPPLY A COMPLETE RISER DIAGRAM |
| | ON HOW GENERATOR WILL BE WIRED INOT NEW |
| | ELECTRICAL SERVICE. WIRING DIAGRAM FROM |
| | MANUFACTURE SUBMITED DOES NOT MEET NEC. |
| | |
| | PLEASE SEE 225.31-225.36 |
| | |
| | 2)NOTE: PLEASE SUBMIT LOAD CALCAULTIONS |
| | FOR SERVICE. PLEASE SEE 702.5 AND |
| | 220.31B FOR SIZING OF GEN FOR SERVICE. |
| | |
| | 3)NOTE: PLEASE SEE PLANS ARE NOT |
| | REQUIRED TO BE DONE BY AND ARCH OR |
| | ENGINEER BUT HOWEVER THEY MAY BE DONE BY |
| | THEM ALSO. |
| | PLEASE SEE FBC 104.2.1 WHICH REQUIRES |
| | THE PRINTED NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR PLANS AND DESIGN. |
| | PLEASE NOTE: PLANS FOR EXISTING HOUSE |
| | ADDITION PERMIT WILL BE REQUIRED TO BE |
| | REVISED TO INCLUDE GEN WORK, HOWEVER |
| | THIS REVSION OF WORK MUST BE DONE BY THE |
| | ARCH OR ENGINEER OF RECORD. |
| | PER FS 481,471 |
| | PLEASE SEE "PROVISO" GIVEN UPON ISSUANCE |
| | OF PERMIT HAS NOT BEEN REVISED AND OR |
| | CORRECTED AS OF THIS REVIEW. |
| | |
| | 4)NOTE: PLEASE BE SURE THE GAS PERMIT IS |
| | EITHER APPLIED FOR OR REVISED IF ONE |
| | ALREADY EXISTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |