| 2004-08-19 00:00:00 | ********** UNSAT ************** |
| | |
| | ** PLEASE SEE SOME NOTES FROM FIRST |
| | REVIEW STILL NEED TO BE ADDRESSED.** |
| | |
| | 1)NOTE: NOTE#1 NO. |
| | PLEASE SEE LOAD CALCULATIONS WERE |
| | SUBMITTED HOWEVER THEY DO NOT MEET NEC |
| | 220.31B. |
| | PLEASE ALSO SEE A/C LOAD IS BEING FIG |
| | AS LIGHTING LOAD? |
| | PLEASE SEE LOAD CALCS ONLY INCLUDE |
| | NEW A/C AND NOT NEW AND EXSITING?? |
| | |
| | 2)NOTE: NOTE #2 NO. NO PANEL SCHEDULE |
| | SUBMITTED SHOWING MIN CIRCUITS. |
| | NOTES WERE SUBMITTED FOR NEW CIRCUITS, |
| | HOWEVER PLEASE SEE THE FOLLOWING FOR |
| | CORRECT LOADS, OCP AND AWG. |
| | 210.52D,210.11C3 FOR BATHS.REQUIRED TO |
| | BE 20A #12 ETC. |
| | PLEASE SEE 210.12 FROM 2002 NEC FOR ARC- |
| | -FAULT PROTECTION. PLANS INDICATE LIGHT- |
| | -ING TO BE PROTECTED.?? SD'S RECEPTS, |
| | LTS. |
| | PLEASE SEE NO OCP/AWG FOR NEW A/C SHOWN? |
| | |
| | 3)NOTE: NOTE #3 OK. |
| | |
| | 4)NOTE: NOTE #4 NO. PLEASE SEE FBC |
| | CHAPTER 34. 3401.7.1.1.2,3401.7.1.2.1 |
| | PLEASE SHOW ALL EXISTING AREAS TO MEET |
| | ABOVE PER ABOVE REQUIREMENTS. |
| | |
| | 5)NOTE: PLEASE SEE ATTACHED COPY OF |
| | FS 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONAL. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS TIME |
| | |
| | 6)NOTE: PLEASE SEE 210.63 FOR LT REQ'D |
| | FOR AHU IN MECH CLOSET.(NEW NOTE) |
| | |
| | |
| | **PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF EACH "OLD" SETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. **** |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |