| 2004-05-14 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04041179 |
| | ADD: 515 N FLAGLER DR# 1200 |
| | CONT: HOLT LEE CONSTRUCTION |
| | TEL: (954)725-4881 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) PLANS DO NOT INDICAE AN ELEVATOR |
| | LOBBY. HIGH RISE REQUIRES ALL ROOMS AND |
| | ENCLOSURES SHALL HAVE AT LEAST ONE |
| | REQUIRED EXIT ACCESSIBLE WITHOUT TRAVEL |
| | THROUGH THE ELEVATOR LOBBY.EXIT STAIRWAY |
| | CHUTES, JANITOR CLOSETS, GUEST ROOMS, |
| | SERVICE ROOMS, ETC, SHALL NOT OPEN INTO |
| | THE ELEVATOR LOBBY. |
| | SEE 412.6.3 FOR SMOKE DETETORS. |
| | |
| | 3) ENTRY DOORS TO THE RECEPTION AREA |
| | BLOCK THE EGRESS |
| | CORRIDOR(1200),1012.1.4DURING ITS |
| | SWING, ANY DOOR IN A MEANS OFEGRESS |
| | SHALL LEAVE UNOBSTRUCTED AT LEAST1/2 OF |
| | THE REQUIRED WIDTH OF THE CORRIDOR. MINI |
| | MUM CLEAR WIDTH OF 22" IS REQUIRED. |
| | |
| | 4) TYPE I/II BUILDING REQUIRES ALL WOOD |
| | BACKING OR BLOCKING TO BE FIRE RESISTANT |
| | TREATED WOOD, 609.1.2. |
| | |
| | 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 6)11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | DOOR TO OFFICE 1220 REQUIRES 12" ON THE |
| | PUSH SIDE, CAGED AREA AND OFICE 1231 |
| | REQUIRE 18" PULL SIDE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |