2004-04-22 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH
 NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 3) ON PAGE E-3 NOTES # 10, 11, AND 13
 ARE INCORECT. THE FIRE ALARM SYSTEM
 CIRCUITS SHALL BE CLASS A OR FULLY
 ADDRESSABLE. ANY SECURITY LOCKS
 INSTALLED ON EXIT DOORS SHALL MEET
 THE REQUIREMENTS OF CHAPTER 7 OF THE
 LIFE SAFETY CODE, 2000 EDITION. DUCT
 SMOKE DETECTORS WHEN ACTIVATED SHALL
 INITIATE AN ALARM NOT A SUPERVISORY
 SIGNAL. PLEASE REVISE PLANS AS NECESSARY
  
 4) NO COMBUSTIBLES ALLOWED IN THE
 RETURN AIR PLENUM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910