| Plan Review Notes For Permit 04041178 |
| Permit Number |
04041178 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-22 00:00:00 | 1) DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH | | | NFPA 241. | | | | | | 2) DEBRIS SHALL BE REMOVED FROM THE | | | SITE DAILY. | | | | | | 3) ON PAGE E-3 NOTES # 10, 11, AND 13 | | | ARE INCORECT. THE FIRE ALARM SYSTEM | | | CIRCUITS SHALL BE CLASS A OR FULLY | | | ADDRESSABLE. ANY SECURITY LOCKS | | | INSTALLED ON EXIT DOORS SHALL MEET | | | THE REQUIREMENTS OF CHAPTER 7 OF THE | | | LIFE SAFETY CODE, 2000 EDITION. DUCT | | | SMOKE DETECTORS WHEN ACTIVATED SHALL | | | INITIATE AN ALARM NOT A SUPERVISORY | | | SIGNAL. PLEASE REVISE PLANS AS NECESSARY | | | | | | 4) NO COMBUSTIBLES ALLOWED IN THE | | | RETURN AIR PLENUM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|