Plan Review Notes For Permit 04041178
Permit Number 04041178
Review Stop B
Sequence Number 1
Notes
Date Text
2004-05-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04041178
 ADD: 515 N FLAGLER DR
 CONT: HOLT LEE CONST
 TEL: ((54)725-4881
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) TYPE I/ II BUILDINGS, ALL BACKING OR
 BLOCKING (WOOD IN WALLS) ARE TO BE FIRE
 RESISTANT TREATED WOOD.
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) PRIVATE RESTROOMS, ARE REQUIRED TO BE
 ADAPTABLE, PROVIDE BACKING IN WALLS.
 11-4.1.3(11)
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026