| 2005-04-11 00:00:00 | ************ UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SEE FS 471.025 AND FAC |
| | 61G15-23.002, WHICH REQUIRES PLANSTO |
| | BE SIGNED WITH AN ORIGINAL SIGNATURE. |
| | PLEASE SEE PLANS AHVE NOW COME BACK IN |
| | WITH A "RUBBER STAMP" FOR ENGINEER'S |
| | SIGNATURE. |
| | PLEASE SEE ONE SET IS ONCE AGAIN |
| | RETAINED FOR FILE AND WILL NOW BE TURNED |
| | OVER TO THE FBPE'S FOR REVIEW OF SAID |
| | VIOLATIONS. PLEASE SEE THESE PLANS WILL |
| | ALSO BE SENT WITH PREVIOUS RETAINED |
| | PLANS AND PLANS FROM OTHER PROJECTS WITH |
| | THE SAME COMMENTS. |
| | |
| | 2)NOTE: PLEASE SEE TITLE BLOCK SHOWS 304 |
| | 37TH =ST AND THE ADDRESS IS INDEED, 904 |
| | 37TH ST. |
| | |
| | 3)NOTE: PLEASE SEE THE 4X FEE WHICH WAS |
| | ACCESSED ON PREVIOUS REVIEW DUE TO |
| | REPEATED CODE COMPLIANCE VIOLATIONS WAS |
| | NOT PAID WHEN PLANS WERE RE-SUBMITTED. |
| | PLEASE SEE FS 553.80(2)(B) WHICH |
| | REQUIRES THIS FEE TO BE PAID "BEFORE" |
| | PLANS MAY BE RE-SUBMITTED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |