2004-12-20 00:00:00BUILDING REVISIONS DENIED
  
 1) ON SHEET A8 DETAIL 11 ON A11 IS
 SPECIFIED FOR THE TRUSS CONNECTION. THE
 CONNECTOR THAT IS SPECIFIED IS A USP
 HLPA 75, WHICH WAS DELETED FROM THE
 REVISED CONNECTOR SCHEDULE. ON SHEET A10
 A TC-2 CONNECTOR IS SPECIFIED FOR AT THE
 SAME TRUSS LOCATION. PLEASE CLARIFY.
  
 2) IN SEVERAL LOCATIONS ON SHEET A10 THE
 LISTED UPLIFT EXCEEDS THE CAPACITY OF
 THE SPECIFIED TRUSS CONNECTOR. PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714