| Plan Review Notes For Permit 04041127 |
| Permit Number |
04041127 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2004-08-11 00:00:00 | DENIED | | | | | | 1) ON SHEET A-9 THE LOWER ROOF PLAN, THE | | | LEFT SIDE OF THE PLAN DOES NOT MATCH THE | | | TRUSS LAYOUT DRAWING. | | | | | | 2) ON SHEET A-9 THE B7 TRUSS ON THE LEFT | | | SIDE HAS CONNECTORS SPECIFIED THAT DO | | | NOT MEET THE UPLIFTS ON THE TRUSS | | | DRAWINGS. | | | | | | 3) TRUSSES B22, B23, B24 AND B28 ON THE | | | RIGHT SIDE OF SHEET A-9 DO NOT HAVE | | | ADEQUATE CONNECTORS. | | | | | | 4) ON THE SECOND FLOOR ROOF PLAN ON | | | SHEET A-10, THE PLANS INDICATE ONE HIP | | | AND ONE GABLE AT THE FRONT OF THE | | | BUILDING. THE TRUSS LAYOUT SHOWS BOTH AS | | | HIP ROOFS. PLEASE CORRECT. | | | | | | 5) ON A-10 TRUSS A29 HAS AN UPLIFT OF | | | 5345# ON THE TRUSS DRAWINGS AND 5070# ON | | | THE PLANS. | | | | | | 6) THE CONNECTOR FOR TRUSS A12 ON THE | | | RIGHT SIDE OF SHEET A-10, HAS THE WRONG | | | TAG. IT SHOULD BE A TC-8 NOT TC-3. | | | | | | 7) ON A-10 TRUSS A8 HAS A CONNECTOR THAT | | | DOES NOT MEET THE UPLIFT SPECIFIED ON | | | THE TRUSS DRAWINGS. | | | | | | 8) ON A-10 TRUSS A29 HAS AN UPLIFT OF | | | 5070# SPECIFIED AND THE TRUSS DRAWINGS | | | LIST AN UPLIFT OF 5345#. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|