| Plan Review Notes For Permit 04041127 |
| Permit Number |
04041127 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-08-05 00:00:00 | TRUSSES DENIED | | | | | | 1) LOWER ROOF PLAN HAS THE CONNECTOR FOR | | | THE AT4 GIRDER TRUSS SPECIFIED IN THE | | | WRONG LOCATION ON SHEET A9. | | | | | | 2) THE UPLIFT IN THE TRUSS DRAWINGS FOR | | | TRUSSES AT16, AT19 AND AT20 EXCEED THE | | | CONNECTORS SPECIFIED FOR THEM ON SHEET | | | A9. | | | | | | 3) THE UPPER ROOF PLAN ON SHEET A10 DOES | | | NOT CORRESPOND TO THE TRUSS LAYOUT. SEE | | | TRUSSES BT 12 AND BT 20 ON LAYOUT. TRUSS | | | BT20 REQUIRES A CENTER BEARING POINT | | | THAT IS NOT SHOWN ON THE PLANS. | | | | | | 4) THE CONNECTORS SPECIFIED FOR TRUSS | | | BT 48 DOES NOT MEET THE REQUIRED UPLIFTS | | | ON THE TRUSS DRAWINGS. |
|