Plan Review Notes
Plan Review Notes For Permit 04041127
Permit Number 04041127
Review Stop P
Sequence Number 2
Notes
Date Text
2004-07-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DO NOT MEET
 CODE REQUIREMENTS, NOR DO THE RISERS
 REFLECT THE FLOOR PLANS.SHT A-14
 - CLEANOUTS SHALL BE INSTALLED AT EACH
 CHANGE OF DIRECTION OF THE BLDG. DRAIN
 GREATER THAN 45 DEGREES. SECTION 708.3.3
 - THERE SHALL BE A CLEANOUT NEAR THE
 JUNCTION OF THE BLDG. DRAIN AND BLDG.
 SEWER. (EACH TIME THE BLDG. DRAIN EXITS
 THE BLDG. - AT KITCHEN AND WHERE THE
 BATHROOMS EXIT SEPARATELY). SECTION
 708.3.5
 - RISERS A & B THE SHOWERS ARE NOT VEN-
 TED IN SECOND BATH. SECTION 901.2.1
 - PLUMBING RISERS C & D SHOWER IS NOT
 TO THE RIGHT OF THE LAV IN BATH #2 AS
 SHOWN ON THE RISER.
 - WATER CLOSET IN MASTER BATH DOES NOT
 SET TO THE RIGHT OF THE TUB AS SHOWN
 ON RISER.
 (SUGGESTION: THE PLUMBING CONTRACTOR CAN
 POSSIBLY INDICATE HOW IT WILL BE INST-
 ALLED AND DRAW A RISER THAT REFLECTS THE
 INSTALLATION).
 2) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
  