Plan Review Notes
Plan Review Notes For Permit 04041127
Permit Number 04041127
Review Stop P
Sequence Number 1
Notes
Date Text
2004-04-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA-98 DESIGN MANUAL
  
 1) SHT A-2 SHOW CLEAR FLOOR SPACE OF THE
 WATER CLOSETS AS SHOWN ON PAGE 7.43. -
 EIGHER 48"X66", 48"X56", OR 60"X56".
 2) SHT A-2 WATER CLOSETS IN BATHROOMS
 SHALL BE 18" OFF WALL. SEE PAGE 7.43,
 EXAMPLES 1, 2, OR 3. SHOW ON FLOOR PLAN.
 3) SHT A-14 PLUMBING RISERS A & B. CLEAN
 OUTS ARE REQUIRED WHERE BLDG DRAIN EXITS
 BUILDING AT KITCHEN AND AFTER WASH
 MACHINE. - SANITARY CROSS FITTINGS ARE
 NOT APPROVED ON HORIZONTAL BUILDING
 DRAINS.
 4) SHT A-14 PLUMBING RISERS C & D DO NOT
 REFLECT THE FLOOR PLAN. SHOWER IS NOT TO
 THE RIGHT OF THE LAV IN BATH #2. KITCHEN
 SINK IS NOT TO THE RIGHT OF BATH #2.
 WATER CLOSET IN MASTER BATH DOES NOT SET
 TO THE RIGHT OF THE TUB.
 5) SHT A-14 PLUMBING RISERS C & D. THE
 WASH MACHINE AND KITCHEN SINK SHALL NOT
 DRAIN THROUGH THE WET VENTED HORIZONTAL
 DRAIN FOR BATH #2. SECTION 909.1.
 THE W/M AND KITCHEN SINK SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT HORIZONTAL
 DRAIN LINE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]