| Plan Review Notes For Permit 04041127 |
| Permit Number |
04041127 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-24 00:00:00 | DENIED: | | | 1.PER 2001 FBC(M) 403.3, OUTSIDE AIR | | | REQUIRED FOR MULTI-FAMILY DWELLINGS IN | | | ACCORDANCE WITH TABLE 403.3. | | | | | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) 307. | | | 2.3. | | | | | | 3.MECHANICAL PLAN INDICATES AHU | | | LOCATED IN THE LAUNDRY ROOM.PLEASE | | | CLARIFY THE FOLLOWING. (A) DRYER - | | | ELECTRIC OR GAS. (B) IS THERE A DOOR | | | SEPARATING THE AHU FROM THE DRYER (C) IS | | | THE RETURN TO THE AHU DUCTED OR IS THE | | | CLOSET AREA A PLENUM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|