Plan Review Notes
Plan Review Notes For Permit 04041127
Permit Number 04041127
Review Stop M
Sequence Number 1
Notes
Date Text
2004-04-24 00:00:00DENIED:
 1.PER 2001 FBC(M) 403.3, OUTSIDE AIR
 REQUIRED FOR MULTI-FAMILY DWELLINGS IN
 ACCORDANCE WITH TABLE 403.3.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M) 307.
 2.3.
  
 3.MECHANICAL PLAN INDICATES AHU
 LOCATED IN THE LAUNDRY ROOM.PLEASE
 CLARIFY THE FOLLOWING. (A) DRYER -
 ELECTRIC OR GAS. (B) IS THERE A DOOR
 SEPARATING THE AHU FROM THE DRYER (C) IS
 THE RETURN TO THE AHU DUCTED OR IS THE
 CLOSET AREA A PLENUM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.