Plan Review Notes
Plan Review Notes For Permit 04041127
Permit Number 04041127
Review Stop B
Sequence Number 1
Notes
Date Text
2004-05-19 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) REVISE PLAN NOTE 10 ON C1. IMPACT
 PROTECTION IS REQUIRED IN WIND BORNE
 DEBRIS REGIONS PER FBC 1606.1.4.
  
 4) SPECIFY THAT THE DOORS FROM THE
 GARAGE TO THE UNITS ARE REQUIRED TO BE
 3/4 HOUR FIRE RATED DOORS WITH CLOSERS.
 SEE FBC 705.1.3.
  
 5) THE WALLS BETWEEN THE GARAGES AND THE
 HABITABLE SPACE ARE REQUIRED TO BE ONE
 HOUR FIRE RATED PER FBC 411.2.6 AND 704.
  
 6) THE WALLS BETWEEN THE GARAGES AND THE
 CONDITIONED SPACE IS REQUIRED TO BE
 INSULATED PER FBC CHAPTER 13.
  
 7) THE TITLE BLOCKS ON THE PLANS CONTAIN
 INCORRECT INFORMATION. THE BUILDING
 NUMBER IS 22 NOT THE LOT NUMBER. THESE
 PLANS ARE NOT MASTERED.
  
 8) SHOW COMPLIANCE WITH FAIR HOUSING ACT
 DESIGN MANUAL. SHOW MINIMUM CLEAR FLOOR
 SPACE AT TOILET OF 48" X 56". CENTER OF
 TOLIET TO BE 18" OFF WALL. SEE PG.7.43.
  
 9) ALL DOORS IN THE UNITS OTHER THAN THE
 ENTRY DOOR, PANTRY DOOR AND MECH. ROOM
 DOOR ARE REQUIRED TO BE USABLE WITH A
 32" NOMINAL CLEAR OPENING OF AT LEAST
 31-5/8 INCH CLEAR. THIRTY-FOUR INCH DOOR
 IS REQUIRED FOR DOORS THAT OPEN LESS
 THAN 180 DEGREES. WALK-IN CLOSET DOORS
 MUST COMPLY. SEE FHADM PG. 3.5.
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 STATE OR LOCAL PRODUCT APPROVALS FOR
 EXTERIOR WINDOWS, DOORS, ROOFING, GARAGE
 DOORS, STORM PANELS, TRUSS CONNECTORS,
 ETC.
  
 11) PRODUCT APPROVAL FOR IMPACT SLIDING
 GLASS DOOR IS LIMITED TO MAXIMUM WIDTH
 OF 8' AND DOES NOT WORK FOR 10'WIDE DOOR
 SPECIFIED ON THE PLANS.
  
 12) SUBMIT KEY PLANS AND INSTALLATION
 SCHEDULES FOR THE STORM PANLES.
  
 13) THE MISSLE IMPACT PROTECTION
 INSTALLATION PLAN NEEDS TO BE SIGNED AND
 NOTARIZED. IT MUST ALSO BE APPROVED BY
 THE BUILDING OFFICIAL.
  
 14) THE ENGINEERING SUBMITTED FOR THE
 BALCONY RAILS AND SCREEN DO NOT MATCH
 THE PLANS.
  
 15) THE LETTER FROM PALM BEACH LIFTS
 NEEDS TO HAVE AN ORIGINAL SIGNATURE.
  
 16) PLEASE SUBMIT TWO COPIES OF ALL
 ITEMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714