| Date |
Text |
| 2004-05-19 00:00:00 | DENIED |
| | |
| | 1)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) REVISE PLAN NOTE 10 ON C1. IMPACT |
| | PROTECTION IS REQUIRED IN WIND BORNE |
| | DEBRIS REGIONS PER FBC 1606.1.4. |
| | |
| | 4) SPECIFY THAT THE DOORS FROM THE |
| | GARAGE TO THE UNITS ARE REQUIRED TO BE |
| | 3/4 HOUR FIRE RATED DOORS WITH CLOSERS. |
| | SEE FBC 705.1.3. |
| | |
| | 5) THE WALLS BETWEEN THE GARAGES AND THE |
| | HABITABLE SPACE ARE REQUIRED TO BE ONE |
| | HOUR FIRE RATED PER FBC 411.2.6 AND 704. |
| | |
| | 6) THE WALLS BETWEEN THE GARAGES AND THE |
| | CONDITIONED SPACE IS REQUIRED TO BE |
| | INSULATED PER FBC CHAPTER 13. |
| | |
| | 7) THE TITLE BLOCKS ON THE PLANS CONTAIN |
| | INCORRECT INFORMATION. THE BUILDING |
| | NUMBER IS 22 NOT THE LOT NUMBER. THESE |
| | PLANS ARE NOT MASTERED. |
| | |
| | 8) SHOW COMPLIANCE WITH FAIR HOUSING ACT |
| | DESIGN MANUAL. SHOW MINIMUM CLEAR FLOOR |
| | SPACE AT TOILET OF 48" X 56". CENTER OF |
| | TOLIET TO BE 18" OFF WALL. SEE PG.7.43. |
| | |
| | 9) ALL DOORS IN THE UNITS OTHER THAN THE |
| | ENTRY DOOR, PANTRY DOOR AND MECH. ROOM |
| | DOOR ARE REQUIRED TO BE USABLE WITH A |
| | 32" NOMINAL CLEAR OPENING OF AT LEAST |
| | 31-5/8 INCH CLEAR. THIRTY-FOUR INCH DOOR |
| | IS REQUIRED FOR DOORS THAT OPEN LESS |
| | THAN 180 DEGREES. WALK-IN CLOSET DOORS |
| | MUST COMPLY. SEE FHADM PG. 3.5. |
| | |
| | 10) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SUBMIT |
| | STATE OR LOCAL PRODUCT APPROVALS FOR |
| | EXTERIOR WINDOWS, DOORS, ROOFING, GARAGE |
| | DOORS, STORM PANELS, TRUSS CONNECTORS, |
| | ETC. |
| | |
| | 11) PRODUCT APPROVAL FOR IMPACT SLIDING |
| | GLASS DOOR IS LIMITED TO MAXIMUM WIDTH |
| | OF 8' AND DOES NOT WORK FOR 10'WIDE DOOR |
| | SPECIFIED ON THE PLANS. |
| | |
| | 12) SUBMIT KEY PLANS AND INSTALLATION |
| | SCHEDULES FOR THE STORM PANLES. |
| | |
| | 13) THE MISSLE IMPACT PROTECTION |
| | INSTALLATION PLAN NEEDS TO BE SIGNED AND |
| | NOTARIZED. IT MUST ALSO BE APPROVED BY |
| | THE BUILDING OFFICIAL. |
| | |
| | 14) THE ENGINEERING SUBMITTED FOR THE |
| | BALCONY RAILS AND SCREEN DO NOT MATCH |
| | THE PLANS. |
| | |
| | 15) THE LETTER FROM PALM BEACH LIFTS |
| | NEEDS TO HAVE AN ORIGINAL SIGNATURE. |
| | |
| | 16) PLEASE SUBMIT TWO COPIES OF ALL |
| | ITEMS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |