| Plan Review Notes For Permit 04041087 |
| Permit Number |
04041087 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-06-10 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)PLEASE CLOUD ALL CHANGES.THE NOTE | | | IN REGARDS TO THE RAILING,RAISED | | | CONFERENCE AREA, SECTION 3-A1 WERE | | | MODIFIED AND NOT INDICATED. | | | | | | 2.)THE RAMP HANDRAILS ARE TO COMPLY | | | WITH FBC1013.7, SHALL EXTEND AT LEAST | | | 18" BEYOND THE TOP AND BOTTOM OF THE | | | RAMP SEGMENT AND SHALL BE PARALLEL WITH | | | THE FLOOR OR GROUND SURFACE.EXTENSION | | | CANNOT ENCROACH UPON 60"X60" LANDING | | | SIZE REQUIRED BY FBC11-4.8.4(3). | | | | | | 3.)SEE PREVIOUS LIST, ITEM #7, IN | | | REGARDS TO FIRE RATED WALLS.THE WALL | | | INDICATED DOES NOT APPEAR TO BE | | | REQUIRED FIRE RATED WALL, SEE PLAN. | | | REVISE. | | | | | | 4.)SEE PLUMBING PROVISO.PLEASE | | | ADDRESS AT THIS TIME. |
|