Plan Review Notes
Plan Review Notes For Permit 04041087
Permit Number 04041087
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-04-16 00:00:001) WHERE DOES THE REAR EXIT LEAD TO.
  
 2) IF STORAGE IS PLANNED FOR UNDERNEATH
 THE PLATFORM, IT WILL BE REQUIRED TO
 BE FIRE SPRINKLER PROTECTED.
  
 3) ALL RAMPS AND STAIRS SHALL HAVE
 HANDRAILS ON BOTH SIDES.
  
 4) PLANS DO NOT INDICATE ANY FIRE
 ALARM EQUIPMENT.
  
 5) NO INFORMATION PROVIDED REGARDING
 THE REMODELING OF THE FIRE SPRINKLER
 SYSTEM.
  
 6) NO INFORMATION REGARDING THE
 INTERIOR FINISH CLASSIFICATION
 FOR WALLS AND CEILINGS.
  
 7) NO INFORMATION REGARDING PORTABLE
 FIRE EXTINGUISHERS.
  
 8) PLEASE INDICATE LOCATIONS AND
 RATINGS OF ALL TENANT SEPARATION
 WALLS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910