Plan Review Notes
Plan Review Notes For Permit 04041087
Permit Number 04041087
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-21 00:00:00************ UNSAT *********
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
  
 2)NOTE: PLEASE SUBMIT MORE INFORMATION
 ON WHAT IS SHOWN AS EXISTING TO BE
 DETERMINED FOR FEED TO NEW 200A MAIN.
 THE 200A MAIN SHOWN AS EXSITING DOES
 NOT SEEM TO BE SHOWN ON BASE BLDG PLANS.
 MORE INFORMATION/LOAD IS NEEDED. 215.5
  
 3)NOTE: PLEASE SEE 250.24/ 250.110 ETC
 FOR EQUIPMENT GROUNDING AFTER FIRST
 MEANS OF DISC..
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 THIS EQUIPMENT IS NOT ON BASE PLANS
 FOR NEW EQUIPMENT.
  
 5)NOTE: PLEASE SEE 210.62 FOR MIN REQ'D
 SHOW WINDOW RECEPTS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING
 ONE SET OF OLD MAY BE REQ'D TO BE RE-
 -SUBMITTED BY OTHER REVIEWERS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]