| 2004-06-25 00:00:00 | **** UNSAT **** |
| | |
| | 1)NOTE: PLEASE SEE A NEW ELECTRICAL |
| | WIRING DIAGRAM IS NOW BEING SUBMITTED |
| | FOR REVIEW. NOTES ARE NOT THE SAME AS |
| | PREVIOUS REVIEWS.PLEASE SEE NEW NOTES. |
| | |
| | 2)NOTE: PLEASE SEE DIAGRAM IS MISSING |
| | WIRE SIZES FOR HEAT PUMP. |
| | |
| | 3)NOTE: PLEASE SEE NEW DIAGRAM IS NOW |
| | ALSO SHOWING A NEW ELECTRICAL PANEL |
| | FROM EXSITING. PLEASE INDICATE WIRE |
| | SIZES, FEEDERS ETC. PLEASE SHOW SIZE |
| | OF PANLE AND SIZE OF OCP FEEDING PANEL. |
| | |
| | 4)NOTE: PLEASE SEE HEAT PUMP IS A |
| | CONTINUOUS LOAD WHICH SHOULD BE SHOWN |
| | AT 125%. 215.3,220.19,230.42 ETC. |
| | |
| | 5)NOTE: PLEASE SEE 220.16 FOR LAUNDRY |
| | CIRCUIT TO BE A MIN OF 1.5KW. |
| | |
| | DUE TO COMMENTS NOT BEING THE SAME FOR |
| | ELECTRICAL AN ADDTIONL 4X FEE WILL NOT |
| | BE ACCESSED FOR ELECTRICAL. |
| | PLEASE SEE COMMENTS FROM PLUMB PLAN |
| | REVIEWER REMAIN THE SAME AND COULD HAVE |
| | ADDITONAL 4X FEE ACCESSED. PLEASE SEE |
| | PLUMB COMMENTS. SAME PLANS CAME BACK FOR |
| | REVIEW. NO NEW SHEETS SUBMITTED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |