| Plan Review Notes For Permit 04041013 |
| Permit Number |
04041013 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-05 00:00:00 | BUILDING REVIEW PROVISO: | | | 1-DETAIL E/4 AND RESIDENTIAL NOTES ON | | | SHEET #2 DON'T MATCH. CLARIFY FASTENER | | | SPACING. SEC. 104.2.1.2 CITY AMENDMENT | | | TO FBC 2001. | | | 2-SECTION A/4: SPECIFY WHERE ARE TABLES | | | 6 AND 8 FOR ROOF TILE FASTENING TAKEN | | | FROM. SEC. 104.2.1.1 CITY AMENDMENTS | | | TO FBC 2001. | | | 3-FLOOD ZONE AO: NEED TO PROVIDE THE | | | ELEVATION CERTIFICATE. |
|