Plan Review Notes
Plan Review Notes For Permit 04040948
Permit Number 04040948
Review Stop P
Sequence Number 1
Notes
Date Text
2004-04-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) ROUTE PLANS TO DBPR HOTEL & RESTURANT
 DIVISTION FOR PLAN REVIEW PRIOR TO RE-
 SUBMITTING TO THE CITY FOR REVIEW. PLANS
 SHALL BE STAMPED AND WORK SHEETS ATTACH-
 ED FOR EACH SET. (850) 487-1395
 SECTION 101.4.7
 2) CONTACT RODNEY COMPO FOR SIZING OF
 THE GREASE INTERCEPTOR. NOTED THAT THIS
 IS AN EXISTING GREASE INTERCEPTOR, BUT
 WASTE ORD # 2938-96 REQUIRES A REVIEW
 BY ENVIRONMENTAL COMPLIANCE MANAGER.
 3) SHT A-1.1 INDICATES DEMOLITION WORK
 BEING DONE. PLEASE SHOW DEMO WORK ON
 PLANS. SECTION 104.2.1
 4) SHT A-1.2 NOTE STATES "NO NEW GAS
 PIPING WORK" BUT SHT P-3 SHOWS GAS
 PIPING AND NEW FIXTURES.PLEASE CORREL-
 ATE PLANS.
 5) SHT P-2 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 SHALL BE LOCATED NEAR THE FIXTURES
 IN AN "EFFECTIVE RANGE" NOT IN THE CEIL-
 ING AS SHOWN. PDI-WH 201 AND MANUF. IN-
 STALL. INSTRUCTIONS.
 6) SHT P-2 WATER HEATER DETAIL. INDICATE
 THE SIZE OF THE WATER HEATER. SUBMIT
 CALCULATIONS FOR BOTTON LOADING OF THE
 ROOF JOISTS FOR THE WATER HEATER. SHOW
 TOTAL WEIGHT ADDED TO JOISTS.
 7) SHT P-3 SEPARATE GAS PERMIT REQUIRED.
 THE FOLLOWING INFORMATION IS REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 8) SHT P-4 GENERAL PLUMBING NOTES #4
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved