| 2004-04-26 00:00:00 | CHECKLIST FOR BUILDING REVIEW: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-SEC. 1005.4.4 FBC 2001 REQUIRES 24"MIN |
| | CLEAR WINDOW OPENING IN HEIGHT. SH24 |
| | AND SH34 ARE TYPICALLY 48" HEIGHT IN |
| | WINDOW FRAME. A)SPECIFY WHICH SIZE OF |
| | "SIMONTON" WINDOWS IS GOING TO BE USED |
| | TO MEET THIS REQUIREMENTS. SEE WINDOW |
| | DIMENSIONS ON PRODUCT APPROVAL AND |
| | REVISE PLANS AS REQUIRED. |
| | B)ALSO, WINDOWS SHOWN ON REAR ELEVATION |
| | AREN'T DRAWN TO SCALE. THEY SCALE TO |
| | BE LIKE SH25 OR SH35 WINDOWS. CLARIFY. |
| | 3-SPECIFY SIZE OF ATTIC ACCESS AS REQ'D |
| | BY SEC. 2309.6 FBC 2001. |
| | 4-PLANS ARE MISSING ALL THE ENGINEER'S |
| | INFORMATION AS REQ'D BY CHAPTER 471 |
| | FLORIDA STATUTES. |
| | 5-SHEET #7: REVISE MIN. SIZE FOR ATTIC |
| | ACCESS. SEE SEC. 2309.6 FBC 2001. |
| | 6-CEILING FAN CREDIT IS TAKEN ON THE |
| | ENERGY CALCS. THEREFORE, SPECIFY |
| | ON PLANS SIZE OF FAN REQUIRED AT EACH |
| | ROOM. TABLE 6-6 CHAPTER 13 FBC 2001. |
| | 7-NEED PRODUCT APPROVAL FOR ENTRY DOOR |
| | WITH TRANSOM ABOVE SINGLE ASSEMBLY AS |
| | SHOWN ON PLANS. |
| | 8-NEED PRODUCT APPROVAL FOR GARAGE DOOR |
| | THAT MEETS THE DESIGN PRESSURES THAT |
| | WERE CALCULATED BY THE ENGINEER. |
| | 9-SHEET #3A: A)ROOF FRAMING PLAN CALLS |
| | FOR CONNECTOR A5 BUT TRUSS ANCHOR |
| | SCHEDULE DOESN'T HAVE A5 CONNECTOR. |
| | SPECIFY/CLARIFY AS REQUIRED. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | B)STUCCO NOTE NEED TO ADDRESS MIN. 7/8" |
| | STUCCO THICKNESS AT FRAMED WALLS AS |
| | REQ'D BY ASTM C-926. |
| | 10-THIS BUILDING PERMIT APPLICATION IS |
| | FOR LOT 48. IMPACT FEES STAMP CALLS |
| | FOR LOT 12. REVISE/CLARIFY AS REQUIRED |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |