| Plan Review Notes For Permit 04040818 |
| Permit Number |
04040818 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-27 00:00:00 | NO MECHANICAL PLANS OR CONTRACTOR | | | INDICATED WITH PERMIT APPLICATION. | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION. | | | 1.PLANS - DUCT/GRILLE SIZE MATERIAL & | | | LAYOUT. | | | | | | 2.OUTSIDE AIR CALCULATIONS PER 2001 | | | FBC(M) TABLE 403.3. | | | | | | 3.PROVIDE EQUIPMENT SCHEDULE. | | | | | | 4.INDICATE CONDENSATE LINE SIZE, | | | MATERIAL AND TERMINATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|