| Plan Review Notes For Permit 04040792 |
| Permit Number |
04040792 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-17 00:00:00 | | | | | | | | | | | | | PER N. MELICK MANUFACTURE INFO | | | NOT REQUIRED FOR 1 & 2 FAMILY HOMES. | | | JULY 17, 2002 OFFICAL INTERPRETATION. | | | THE FIELD INSPECTOR SHALL VERIFY THE | | | INSTALLED EQUIPMENT INPUT DOES NOT EX- | | | CEED THE PIPE SIZING. | | | | | | IF DRYER ROOM IS A CONFINED SPACE, | | | OPENINGS REQUIRED PER SECTION 304.3.1 0R | | | SECTION 304.3.2 SHALL BE INSTALLED. | | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | MINIMUM 3,750 CUBIC FEET REQUIRED FOR | | | WATER HEATER ROOM. |
|