2004-05-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 040407781)
 ADD: 201 S NARCISSUS AV
 CONT: MC LAREN CONST
 TEL: (561)686-6500
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 803.4 FOAM PLASTICS. FOAM PLASTICS SHALL
 NOT BE USED AS INTERIOR FINISH.
 EXCEPTION:
 A) THE MINIMUM DENSITY IS 20LB/CU FT .
 B) THE MAXIMUM THICKNESS OF THE TRIM IS
 1/2" AND THE MAXIMUM WIDTH IS 4".
 C) THE TRIM CONSTITUTES NO MORE THAN
 10% OF THE AREA OF ANY WALL OR
 CEILING.
 D) THE FLAMESPREAD RATING DOES NOT EX-
 CEED 75 WHEN TESTED PER ASTM E 84.
  
 2) MARBLE FIREPLACE:
 PROVIDE ADDITIONAL INFORMATION:
 IS THIS A ACTIVE FIREPLACE WITH A MARBLE
 SURROUND?
 FALSE FIREPLACES, 2807, FALSE FIREPLACES
 MAY BE USED IN CONNECTION WITH LISTED
 GAS OR ELECTRIC HEATERS, PROVIDED SUCH
 FIREPLACES ARE CONSTRUCTED OF NONCOMBUST
 IBLE MATERIALS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026