| Plan Review Notes For Permit 04040679 |
| Permit Number |
04040679 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-06-01 00:00:00 | DENIED: | | | RESPONSE LETTER FROM KAMM CONSULTING: | | | DESIGN CAPACITY IS LESS THAN 2,000 CFM, | | | THEREFORE DUCT SMOKE DETECTORS & ALARM/ | | | STROBE IS NOT REQUIRED. | | | | | | PLEASE PROVIDE MANUFACTURER SUBMITTAL | | | DATA FOR THE CARRIER AHU & CU #4. | | | PROVIDE A LETTER FROM THE MANUFACTURER'S | | | ENGINEER SPECIFYING UNDER NO CONDITIONS | | | WILL THE EQUIPMENT EXCEED 2,000 CFM. | | | THE LETTER SHALL BE SIGNED, SEALED & | | | DATED BY THE ENGINEER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|