| Plan Review Notes For Permit 04040679 |
| Permit Number |
04040679 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-05-21 00:00:00 | 1) DOOR 113 STILL OPENS INTO CORRIDOR | | | 112. THIS DOOR IS APPROXIMATELY THREE | | | FEET WIDE AND THE CORRIDOR IS ONLY FOUR | | | FEET TEN INCHES THUS LEAVING 32 INCHES | | | FOR EXITING. IN BUSINESS OCCUPANICES, | | | FORTY FOUR INCHES IS REQUIRED. ALSO | | | IT APPEARS THAT THE EXIT ROUTE HAS | | | BEEN CHANGED BUT THE ELECTRICAL PLANS | | | STILL SHOW TWO EXIT SIGNS FROM THE | | | WORK AREA/WORK ROOM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|