| 2004-04-22 00:00:00 | DENIED: | | | PER 2001 FBC(M) 606.2.1, DUCT SMOKE | | | DETECTORS ARE REQUIRED IN SYSTEMS THAT | | | HAVE THE DESIGN CAPACITY GREATER THAN | | | 2,000 CFM.PROVIDE LETTER FROM | | | MANUFACTURERS ENGINEER INDICATING THAT | | | UNDER NO CIRCUMSTANCE, WILL AHU-4 BE | | | ABLE TO PROVIDE GREATER THAN 2,000 CFM. | | | | | | FAN SHUTDOWN SHALL HAVE NOTIFICATION TO | | | ALARM/STROBE IN NORMALLY OCCUPIED AREAS. | | | 2001 NFPA 90A 6.4.4.3 (1). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|