2004-06-16 00:00:00****** NOTES REDLINED ******
  
 PLANS ARE NOW SHOWING AN EQUIPMENT
 GROUNDING TO METER, FROM METER TO MAIN,
 PLEASE SEE 250.24/250.6. AN EQUIP GRND
 IS ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
  
 PLEASE SEE MIN OCP FOR 5KW HEAT WOULD
 BE 30A AND MAX OF 150%.
 PLANS SHOW 50A'S, THIS WILL BE REQUIRED
 TO BE FEILD VERIFIED.
  
 ALL REV'S TO BE SUBMITTED BEFORE ROUGH.